Sutron XLink 100/500 Logging Transmitter

Añadir al presupuesto
Imagen de: Sutron XLink 100/500 Logging Transmitter

Multi-Sensor Input Logger with data transmission via lridium or Cellular

Sutron’s XLink product family offers a cost-effective Wi-Fi enabled datalogger with data transmission via Iridium or Cellular. Ideal for use with multiple digital and analog sensors supporting basic or advanced monitoring applications. The product comes in two models tailored to fit different application and budget requirements. The XLink 100 and XLink 500 carry over all the great capabilities from its predecessor family (CDMALink, HSPALink, GPRSLink, IridiumLink).

  • USB-Host, RS-232, Cellular, Data Logger, RS-232 and RS-485, Switchable SDI-12 power, Iridium
  • Plug and play modem, custom programming with Python Scripts (XLlink500), up to 32 measurements, log up to 1,000,000 readings, USB flash drive, secure communication (TLS 1.2 ciphers), multiple interfaces and protocols (HTTP,TCP/IP,FTP), and 3 levels of security to configure, perform maintenance or access data
  • Yes
  • SDI-12, RS-232, RS-485
GENERAL INFORMATION
Dimensions
XLink500-1, XLink100-1 Inches: 4.5 x 6.2 x 1.6 (cm: 11.4 x 15.8 x 4.1)
NEMA-4 (IP66) Inches: 7.3 x 9.5 x 5.2 (cm: 18.5 x 24.2 x 13.2)
Weight (XLink500-1) 1 lbs. (0.5 Kg)
IP rating IP66 (NEMA variants)
Operating temperature 40 °C to +70 °C (-40 °F to +158 °F)
Compliance CE, FCC, ISED
_________________
POWER REQUIREMENTS
Voltage 9-2 0 VDC; 10-16 VDC for SDI-12 Compliance
Quiescent < 1 mA typ. @12.5 VDC
SDI-12 (DEDICATED INTERFACE)
Compliance V1.3 data recorder
Power 500 mA, short-circuit protected
_________________
ANALOG – SINGLE ENDED (XLink 500 ONLY)
Number of inputs 2
Range* 0-5V
Accuracy @ 25 °C 0.04 % typ. FS
Resolution 0.3 µV
_________________
ANALOG – DIFFERENTIAL (XLink 500 ONLY)
Number of Inputs 2
Range* ±39 mV, ±312 mV, ±2.5 V
Accuracy @ 25°C 0.04 % typ. FS over 2.5 V
Resolution 0.3 µV @ ±2.5 V scale
_________________
ANALOG – 4-20 mA (XLink 500 ONLY)
Number of inputs 1
Range 0-22 mA
Accuracy @ 25°C 0.14 % FS
Load Internal 200 ohms
_________________
DIGITAL – INPUTS/OUTPUTS
Number of inputs 2
Input type 0-15 V, optional low-level input Status, counter, frequency
Max input frequency 10 KHz, optional debouncing, internal pull
Number of outputs 1
Output types On/off/ pulse
Open collector w/100 ohm limiting resistor.
100 mA, 15V max
_________________
OTHER INPUTS/OUTPUTS
Precision analog reference (XLink 500 only) 2 terminals, 2.5 V, 10.0 mA (total)
Switch 12V 1A, 1 port, overloaded protected
Protected 12V (XLink 500 only) 0.75 A, 1 port
RS-485 1 port; SDI-12, ModBus, custom communications with Python
RS-232 DB9; terminal interface, User interface, ModBus, custom communications with Python
USB Device (Micro B) 1 port; PC / MAC communication using Sutron’s LinkCOMM
USB Host (Type A) 1 port; setup, firmware update, log download using a USB flash drive
Celluar Modem Global HSPA (3G)
Frequency 850 MHz; 1700 MHz; 1900 MHz Band
_________________
* * Nominal. Guaranteed Analog Input Range Over Temperature Is 0–4.98 V, ± 2.49 V, ±311 mV, ±38.9 mV.
Imagen de Sutron XLink 100/500 Logging Transmitter
Imagen de Sutron XLink 100/500 Logging Transmitter
Imagen de Sutron XLink 100/500 Logging Transmitter
Imagen de Sutron XLink 100/500 Logging Transmitter
Imagen de Sutron XLink 100/500 Logging Transmitter
Imagen de Sutron XLink 100/500 Logging Transmitter

Contáctenos

Si está pensando en llevar a cabo un proyecto, desea adquirir instrumentación, quiere más información al respecto de los servicios de DILUS o desea mas información sobre Sutron XLink 100/500 Logging Transmitter, deje sus datos. El equipo se pondrá en contacto con usted a la mayor brevedad posible.



    Responsable: DILUS INSTRUMENTACIÓN Y SISTEMAS S.A.
    Finalidad: Recogida de datos personales para poder atender su solicitud
    Legitimación: Consentimiento del interesado
    Destinatarios: No se cederán datos a terceros, salvo obligación legal y salvo las entidades que colaboran con DILUS INSTRUMENTACIÓN Y SISTEMAS S.A. para la prestación de servicios y la correcta gestión de la entidad, en cuyo caso, solo con las finalidades y los usos exclusivamente necesarios para el desarrollo de su actividad y para el que fueron requeridos sus servicios, no pudiendo usar los mismos para un fin distinto
    Derechos: Acceder, rectificar o suprimir los datos, así como otros derechos, como se explica en la información adicional en la política de privacidad